SC5000HV-MV PCS

DC side

Max. DC voltage
1500 V
Min. DC voltage
800V
DC voltage range for nominal power
800 – 1500 V
Max. DC current
7016 A
Max. DC power
5612kW

AC side (Grid)

AC output power
5500 kVA @ 45 ℃ / 5000 kVA @ 50 ℃
AC voltage range
10 – 35 kV
Nominal grid frequency / Grid frequency range
50 Hz / 45 – 55 Hz, 60 Hz / 55 – 65 Hz
AC current THD
< 3 % (at nominal power)
DC current injection
< 0.5 % In
Power factor at nominal power
> 0.99 / 1 leading – 1 lagging
Adjustable reactive power
-100% – 100%

AC side (Off-Grid)

Nominal AC voltage
550 V
AC voltage range
484 – 625V
DC voltage component
< 0.5 % Un (Linear balance load)
Unbalance load capacity
100%
Nominal voltage frequency / Voltage frequency range
50 Hz / 45 – 55 Hz, 60 Hz / 55 – 65 Hz

Efficiency

Max. charge efficiency
98.90 %
Max. discharge efficiency
98.50 %

Transformer

Transformer rated power
5000 kVA
Transformer max. power
5500 kVA
LV / MV voltage
0.55 kV / 10 – 35 kV
Transformer Vector
Dy1y1
Transformer cooling type
ONAN(Oil Natural Air Natural)
Oil type
Mineral oil(PCB free) or degradable oil on request

Protection

DC input protection
Load break switch + fuse
Inverter output protection
Circuit breaker
AC output protection
Circuit breaker
Overvoltage protection
DC Type II / AC Type II
Grid monitoring
Ground fault monitoring
Insulation monitoring
Overheat protection

General Data

Dimensions
12,192 × 2,896 × 2,438 mm 480 × 114.01 × 95.98 in
Weight
31,297.87 kg 68,999.99 kg
Degree of protection
IP54
Auxiliary power supply
220 Vac, 1.5 kVA / Optional: 480 Vac,30 kVA
Operating ambient temperature range
-30 to 60 ℃ (> 50 ℃ derating)
Allowable relative humidity range (non-condensing)
0 – 95 % (non-condensing)
Cooling method
Temperature controlled forced air cooling
Max. operating altitude
1000 m(standard) > 1000 m (optional)
Display
Touch screen
Communication
Standard: RS485, CAN, Ethernet; Optional: optical fiber
Compliance
CE, IEC 62477,IEC 61000
Grid Support
L/HVRT, L/HFRT, active & reactive power control and power ramp rate control